How to repair hot-dip galvanizing according to ISO 1461 and ASTM A780
Hot-dip galvanizing protects steel for decades, but it isn't invulnerable. Impacts during transport, welds made on site, cuts, drill holes or areas not covered in the bath leave the steel bare. If they aren't repaired properly, that's where corrosion starts. We explain what the two reference standards require and how to make a compliant repair.
What ISO 1461 says
ISO 1461:2022 regulates hot-dip galvanizing of iron and steel articles and sets clear limits for the repair (renovation) of uncoated or damaged areas:
Size: each area to be repaired may be at most 10 cm².
Total: the sum of repaired areas must not exceed 0.5% of the total surface area of the part. Above that, the normal approach is to regalvanize, unless otherwise agreed between the parties.
Methods: zinc-rich paint or paste, low-melting-point zinc stick or thermal-spray zinc metallizing (ISO 2063).
Thickness: the repair coating must be at least 100 µm, unless otherwise agreed (for example, if the part is to be painted afterwards).
The 2022 edition no longer requires the paint pigment to meet ISO 3549, but it keeps the essential point: the repair must give sacrificial (cathodic) protection to the steel, like the galvanizing itself.
What ASTM A780 says
ASTM A780 is the US practice for repairing damaged or uncoated areas of hot-dip galvanizing. It allows three methods: zinc-based solders, zinc metallizing and zinc-rich paints.
For paints, it considers those with 65 to 69% zinc dust in the dry film and those above 92% equally effective. The repair thickness is set by the specification applicable to the project.
Step by step: how to repair with zinc paint
Assess the damage. Measure each area and the total. If you exceed the ISO 1461 limits, consider regalvanizing or agree the repair with your client or the site management.
Prepare the surface. Remove rust, mill scale, welding slag and paint residues. Ideally, blast-clean to grade Sa 2½ (ISO 8501-1); on site you can use sandpaper or a 180-220 grit flap disc. Also degrease and clean a margin of sound galvanizing around the area.
Apply without delay. Coat as soon as possible after surface preparation: within 12 hours outdoors or 48 hours indoors at most, so that rust doesn't reappear.
Apply in coats. Use a natural-bristle brush, solvent-resistant roller, spray gun or aerosol. Apply a thin first coat and then coats of 60-80 µm up to the required thickness, overlapping a few centimetres onto sound galvanizing.
Respect drying times. With GALVANOL, touch-dry is about 20 minutes at 20 °C, full drying 4 hours and full cure 72 hours.
Measure the thickness. Check the dry film thickness with a magnetic gauge. To meet ISO 1461 you need at least 100 µm, unless otherwise agreed.
Why GALVANOL fits these standards
GALVANOL is a single-component cold galvanizing product that we make in Gironella (Barcelona). Its dry film contains a minimum of 96% zinc, above the 92% that ASTM A780 considers effective, with 99.995% pure zinc dust (ISO 752). It provides active cathodic and barrier protection, like hot-dip galvanizing.
For small repairs such as welds, cuts or assembly bolts, the spray format lets you work quickly without a brush. For larger surfaces, the can or bucket is applied by brush, roller or spray gun.
Common mistakes to avoid
Painting over rust or grease: zinc paint needs direct contact with the steel to protect it.
Falling short on thickness: a single thin coat rarely reaches 100 µm.
Using low-content "zinc" paints or silver aluminium paints as a repair: they give colour, but no cathodic protection.
Thinning with solvents not specified by the manufacturer.
Do you have a project or solar park with galvanizing repairs? See the technical data sheets on the Products page or write to us at info@galvanol.eu and we'll help you calculate the quantity you need.
For a step-by-step guide to an on-site repair, read how to repair welds and cuts on galvanized steel. And for the American standard, GALVANOL and ASTM A780.
This article is a general guide. For each project, the technical specification and the requirements agreed with the client take precedence.